FIBREroll S200

Textile roller smoke-proof fire shutter with the S200 classification

Fire resistance:

EW 60-C0S200

 

Textile roller shutters are used to separate two adjacent fire compartments in the event of a fire or to eliminate a fire-hazardous area while retaining openings in the perimeter shell of the object.

For cases where smoke resistance is required in addition to fire resistance, a smoke-proof fire extinguisher shutter with S200 classification has been developed according to EN 1634-3.

Due to their minimal space requirements, textile roller shutters can be used in cultural, educational, sports, transport, residential and office buildings, in shopping centers in combination with security grids and also in underground garages, industrial buildings, halls, etc.

Under normal circumstances, the fabric is wound in a cover that is positioned so that it does not interfere with standard operation (usually above the ceiling). The shutter thus requires no more space on the sides of the opening, unlike sliding doors and gates.

The basic requirement for fire shutters is their fire resistance. Rolling fire shutters FIBREroll S200 have a fire resistance of up to EW 60-C0S200.


Certification

Fire curtain FIBREroll S200 has been successfully tested in fire testing center FIRES s.r.o., classified as per EN 15269-11 and EN13501-2, assessed as per EN 13241+A2 and EN 16034 and is covered by CE certificate No. 1396‑CPR‑0154 (a subtype of FIBREroll).

For more information, contact projekce@avaps.cz

Manufacturer issues declaration of performance for individual orders in compliance with Regulation of the European Parliament and Council (EU) No. 305/2011.


Technical information:

  • Smoke-tight version of FIBREroll textile fire curtain with S200 classification
  • Made of special fire-resistant textile 0.7 thick, reinforced by stainless steel wires with surface coating and aluminium reflecting coating (foil) to increase fire resistance
  • Certified dimensions: maximum total width 3 m, maximum total height 3 m
  • Minimum total width 1000 mm
  • Designed for face fixing or fixing between assembly (possible combination of both), fixing into concrete, masonry or steel profiles with required fire resistance
  • Standard dimension of the box is 230 x 230 mm (W x H), the smoke-tight bottom rail is lowered 150 mm under the box, it can be covered on customer's request - the box size in this case is 230 x 380 mm (W x H)
  • Very light (curtain 3 x 3 m approx. 160 kg)
  • Controlled electrically by means of a tube drive (230 V)
  • Control panel AOP (Avaps Operation Panel) including emergency closure button
    • System designed in accordance with EN 14637
    • Ensures electronic control of individual curtain functions
    • “Fail safe” - safe gravity closure even in the event of a power failure, status monitoring and fault evaluation (short circuit, cabling failure, undervoltage, preload,…)
    • Fire detection options: local Fire Alarm System (potential-free contact) or local detection (3 or 6 sensors depending on the closure width)
    • Contains its own back-up power source (accumulator) to prevent unwanted closing of the curtain in case of power failure, including a cyclic charging system that extends battery life
    • According to customer requirements can be supplemented with:
      • key switch, lockable button
      • optical and acoustic signalling
      • signalling of conditions to external devices
  • Closing speed is approximately 100 mm/s
  • Steel parts are made from galvanized metal, standardly powder coated in RAL 9006 (white aluminium) or RAL 9010 (white), alternatively, atypical coating according to the RAL sampler possible at the customer's request.